Optimum Settings for Automatic Controllers, by J.G. Zieger and N. B. Nichols and
Wikipedia
slice:z-n
This is an old revision of the document!
Table of Contents
Ziegler-Nichols Loop Tuning
The Ziegler-Nichols loop tuning protocol1) is a simple method to establishing the loop parameter values for a PI or PID control loop. This protocol is designed to optimize the loop for disturbance rejection.
Links
Click here for the SLICE-QT Manual.
Click here for the SLICE-QT Quick Start Guide.
Click here for the SLICE-QT API.
Click here for the SLICE-QT web page.
Instructions
There is the possibility for the loop to go unstable at too high gain. Use caution as gain is increased. |
- From the Home Screen, touch the Channel icon for the loop to be tuned
- Touch Settings > PID Params
- Choose a Set Point temperature
- Set Proportional Gain (KP) to 0
- Turn off Integral and Differential portions of the loop (TI & TD, respectively)
- While monitoring the error in temperature on rolling graph on the SLICE-QT display or an external oscilloscope, slowly increase KP until the error begins to oscillate
-
- You can use the two rotary knobs or touch & drag the cursors on the touch screen
- Note KP where oscillation begins, KP, cr
- Use the following table to set the values of KP, TI, and TD
slice/z-n.1554247199.txt.gz · Last modified: 2021/08/26 14:26 (external edit)